Brief instructions
SIMATIC - ET 200pro motor starters
2-4 GWA 4NEB 950 5661-02 DS 06
Mounting order
A precise mounting description can be found for the following:
IM 154 Installation of DP High Feature and digital modules in the manual
’ET 200pro Distributed I/O Device
Installation of rear wall bus modules in chapter 3.4
Installation of repair switch modules and motor starters in chapter 3.5
For mounting, proceed as follows:
1. Install the module carrier on a solid base.
2. Start installing the individual modules onto
the module carrier from the left.
Observe the following order:
- IM 154-. interface module DP High Feature
- 8 DI 24V DC electronics module
- Rear wall bus module for repair switch module
- Rear wall bus module for DSe direct starters; Standard
- Terminating module
3. Place the relevant function module onto the rear wall bus module and
secure using bolts.
4. On the IM 154-. DP High Feature interface module, set the PROFIBUS
address 6.
Figure 2-2: Set PROFIBUS address 6
OFF ON
64
32
16
8
4
2
1
Coding switch under screw cover
on the front side
PROFIBUS address 6
Page view 33