Commissioning and diagnostics
SIMATIC - ET 200pro motor starters
GWA 4NEB 950 5661-02 DS 06
4-13
Output signals
DO 0.0 Motor cw DO 1.0 Not used
0 Motor off
1 Motor on
DO 0.1 Motor ccw (for RSe) DO 1.1 Not used
0 Motor off
1 Motor on
DO 0.2 Brake actuation DO 1.2 Not used
0 No drive
- brake active
- motor braked
1Drive
- brake released
- motor unbraked
DO 0.3 Trip reset (edge 0 1) DO 1.3 Not used
0 Trip reset inactive
1 Trip reset active
DO 0.4 Emergency start DO 1.4 Not used
0 Not active
1Active
DO 0.5 Self-test DO 1.5 Not used
0 Not active
1Active
DO 0.6 Not supported DO 1.6 Not used
DO 0.7 Not used DO 1.7 Disable quick stop
1)
0 not activated
1 activated
1) High feature starter only