Siemens HF 35M 562 B Specifications Page 158

  • Download
  • Add to my manuals
  • Print
  • Page
    / 262
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 157
Device functions
SIMATIC - ET 200pro motor starters
10-20 GWA 4NEB 950 5661-02 DS 06
10.7 Inputs (can only be parameterized with high feature motor starters)
Description
With the ’Inputs device function, the motor starter can run various
actions that can be parameterized. The signals at the digital inputs are evaluated
for this purpose. The inputs can be wired directly to sensors (PNP) in 2-core and
3-core technology.
The input actions of the individual digital inputs affect the motor starter func-
tions independently from one another (= OR operand)
10.7.1 Device parameters
Input signal extension
A short input signal can be extended using this parameter in comparison to
the actual input signal present. This makes it possible to ensure a reliable trans-
fer (compensation of bus transfer times and processing time in the control).
Range: 0 milliseconds to 200 milliseconds
Input signal delay
For interference immunity reasons, a debounce time can be set for the inputs.
Range: 10 milliseconds to 80 milliseconds
n signal input
This device parameter is used to specify whether or not the input level of
the digital inputs is to be saved.
retentive, e.g. self-holding operation
non-retentive, i.e. inching operation.