Commissioning and diagnostics
SIMATIC - ET 200pro motor starters
4-12 GWA 4NEB 950 5661-02 DS 06
4.5.2 Process image for motor starters
Input signals
DI 0.0 Ready (automatic) DI 1.0 Motor current I
act
2)
0 Starter not ready via host /
PLC
Bit 0
1 Starter can be operated
by host
DI 0.1 Motor on
1)
DI 1.1 Motor current I
act
2)
0Off Bit1
1 On (clockwise/counterclock-
wise rotation)
DI 0.2 Group fault
(short-circuit / overload)
DI 1.2 Motor current I
act
2)
(If one or more faults
described in table 4-6 occur,
"Group fault" is reported
irrespective of whether the
"Group diagnosis" parameter
(see chapter 7.6.1 and
chapter 8.2.4) is set to
"Disable" or "Enable").
Bit 2
0No faults
1Fault
DI 0.3 General warning DI 1.3 Motor current I
act
2)
0No warning Bit3
1Warning
DI 0.4 Input 1 DI 1.4 Motor current I
act
2)
0 Not active Bit 4
1Active
DI 0.5 Input 2 DI 1.5 Motor current I
act
2)
0 Not active Bit 5
1Active
DI 0.6 Input 3 DI 1.6 Manual local operating mode
0 Not active 0 Not active
1 Active 1 Manual operation local
DI 0.7 Input 4 DI 1.7 Ramp operation
(for soft starter)
0 Not active 0 Not active
1Active 1Active
1) Signal is 1 if the motor current is >18.75% of the set rated current
2) See chapter 10.3.1
For a description of the parameters, see chapter 10.3