Data formats and data records
SIMATIC - ET 200pro motor starters
GWA 4NEB 950 5661-02 DS 06
D-15
6
0
Earth fault detected
Earth fault current present
Signalling bit is updated continuously
6
1
Earth fault shutdown F24 Earth fault current present and shutdown
Signalling bit is cleared when the shutdown cause has
been eliminated and acknowledged with trip reset
6
2
Quick-stop active
2)
F26,
F24
Quick-stop is present and shutdown
Signalling bit is cleared if the shutdown cause
is eliminated and acknowledged with trip reset
6
3
Sensor supply overload
2)
F26,
F24
Sensor supply overload present and shutdown
Signalling bit is cleared when the shutdown cause
has been eliminated and acknowledged with trip
reset
6
4
Trip reset completed
Signalling bit is cleared by updating or via trip reset
in ready-for-operation status
6
5
Trip reset not possible
Shutdown cause still present!
Signalling bit is cleared by updating (new trip reset)
or via trip reset in ready-for-operation status
6
6
Slave pointer deleted
Signalling bit is always cleared when acknowledged
with ’Trip Reset’.
6
7
Electronics power supply
too low
Signalling bit is automatically cleared when
the shutdown cause is eliminated
Communication
7
0
Bus fault
Response monitoring for DP interface expired
Signalling bit is updated continuously
7
1
CPU/master STOP
PLC program is no longer being processed
Signalling bit is updated continuously
7
2
22
0
Automatic operating mode
redundant to bit 7.2
Automatic (PLC control)
Signalling bit is updated continuously
7
3
22
1
Manual bus operating mode
redundant to bit 7.3
Manual operation via field bus (B&B control)
Signalling bit is updated continuously
22
2
Manual bus - PC controlling
7
4
22
3
Manual local operating mode
redundant to bit 7.4
Manual operation via local device interface
(B&B control)
Signalling bit is updated continuously
7
5
Reserved = 0
7
6
Lost connection in manual
operating mode
the associated communication connection was
interrupted during manual operation
Signalling bit is updated continuously
7
7
Process image fault F26,
F24
Process image of the outputs contains nonallowable
bit combination
Signalling bit is automatically cleared when
the shutdown cause has been eliminated
Byte Signalling bit F-no.
1)
Meaning / Acknowledgement
Table D-12: DS92 – Read device diagnostics (Contd.)