Data formats and data records
SIMATIC - ET 200pro motor starters
D-28 GWA 4NEB 950 5661-02 DS 06
—30
0…7
Blocking current 150 … 1000 50% 1000%
DSe, RSe
(HF); sDSSte/
sDSte,
sRSSte/sRSte
31 Upper current pre-
warning limit value
not used
—32
0…3
Blocking time 1s 5 s 0.5 s 1 s
DSe, RSe
(HF); sDSSte/
sDSte,
sRSSte/sRSte
7
4…5
32
4…5
Response with power
supply
Switching element
missing
Group fault [0]
Group fault
only with On
command [1]
Group warning [2]
—[0]
all starters
7
7
32
6
Response to current
limit violation
warning [0]
shutdown [1]
—[0]
DSe, RSe
(HF); sDSSte/
sDSte,
sRSSte/sRSte
7
6
32
7
Response to residual
current detection
warning [0]
shutdown [1]
—[1]
all starters
—33
0…1
Response with power
switch off
not used
—33
2…3
Response with
switching element
overload
not used
—33
4…7
Asymmetry pre-
warning limit value
not used
—34
0…2
Asymmetrical
limit value
30 … 60 10% 30 %
DSe, RSe
(HF); sDSSte/
sDSte,
sRSSte/sRSte
—34
3…5
Reserved
7
3
34
6
Response with
asymmetry
warning [0]
shutdown [1]
—[1]
all starters
—34
7
Response with
earth fault
not used
—35
0…7
Earth fault
prewarning limit value
not used
—36
0…7
Interlock time 0s 60 s 1 s 0 s RSe (HF),
sRSSte/
sRSte
—37
0…7
Input signal extension 0…200 ms 10 ms 0 ms
DSe, RSe
(HF); sDSSte/
sDSte,
sRSSte/sRSte
GSD
byte
DS 131
Byte
Parameters Value range
Incre-
ment
Factory
setting
Relevant to
Table D-20: DS131 – Device parameters (Contd.)