Device functions
SIMATIC - ET 200pro motor starters
GWA 4NEB 950 5661-02 DS 06
10-27
10.7.2 Input parameters – settings
The table below shows the device parameter settings:
Device parameters Default setting Adjustment range
Input signal extension 0 milliseconds 0 milliseconds to
200 milliseconds
Increment: 10 ms
Input signal delay 10 milliseconds 10 milliseconds to
80 milliseconds
Increment: 10 ms
Input 1 - level NO NO contact /
NC contact
Input 2 - level
Input 3 – level
Input 4 – level
Input 1 - action No action No action / shutdown
without restart / shut-
down with restart /
shutdown cw end
position / shutdown
ccw end position /
group warning / man-
ual local operating
mode / emergency
start / motor cw /
motor ccw / quick
stop / trip reset
Cold run
Input 2 - action
Input 3 – action
Input 4 – action
Input 1 – signal non-retentive retentive /
non-retentive
Input 2 – signal
Input 3 – signal
Input 4 – signal
Table 10-15: Input parameters – settings