Commissioning and diagnostics
SIMATIC - ET 200pro motor starters
4-14 GWA 4NEB 950 5661-02 DS 06
Log book entries
The following log book entries are stored in the starter and can be exported via
’ES Motor Starter’ from version 2006:
• DS 72 device fault
• DS 73 trips
• DS 75 events
The 3 log books are organized as a ring buffer each of 126 bytes. The entries are
made together with the corresponding current operating hours of the device.
For each entry, 6 bytes are required, meaning that the last 20 entries remain
legible.
Format of the entries:
Measurements (DS 94)
The measurements give the current operating status of the motor.
Measurements are transient values.
The following data are saved in data record 94 on the motor starter:
• Remaining cool-down time of the motor
1)
• Motor heating
•Asymmetry
1)
• Phase current I
L1
(eff)
• Phase current I
L2
(eff)
• Phase current I
L3
(eff)
• Phase current I
L1
(%)
• Phase current I
L2
(%)
• Phase current I
L3
(%)
• Time-based triggering of the thermal motor model
Byte Meaning
0-3 Operating hours on device (h:mm:ss; storage in 1 s increments)
4-5 ID no. of device fault, trip, event
Table 4-5: Log book entries
1) only with HF starters