Commissioning and diagnostics
SIMATIC - ET 200pro motor starters
4-14 GWA 4NEB 950 5661-02 DS 06
Log book entries
The following log book entries are stored in the starter and can be exported via
’ES Motor Starter from version 2006:
DS 72 device fault
DS 73 trips
DS 75 events
The 3 log books are organized as a ring buffer each of 126 bytes. The entries are
made together with the corresponding current operating hours of the device.
For each entry, 6 bytes are required, meaning that the last 20 entries remain
legible.
Format of the entries:
Measurements (DS 94)
The measurements give the current operating status of the motor.
Measurements are transient values.
The following data are saved in data record 94 on the motor starter:
Remaining cool-down time of the motor
1)
Motor heating
•Asymmetry
1)
Phase current I
L1
(eff)
Phase current I
L2
(eff)
Phase current I
L3
(eff)
Phase current I
L1
(%)
Phase current I
L2
(%)
Phase current I
L3
(%)
Time-based triggering of the thermal motor model
Byte Meaning
0-3 Operating hours on device (h:mm:ss; storage in 1 s increments)
4-5 ID no. of device fault, trip, event
Table 4-5: Log book entries
1) only with HF starters