Applications
SIMATIC - ET 200pro motor starters
C-8 GWA 4NEB 950 5661-02 DS 06
C.2 SAFETY applications
Safety note
With designs for safety applications in categories 2 to 4, a safety local repair
switch module should be used in combination with a 400 V trip module.
An automatic re-start in connection with an emergency stop is not permitted.
C.2.1 1-channel emergency stop with monitored START
The example below shows a design with emergency stop with monitored
START for category 2.
Caution
Please ensure that both coding switches are in the correct position in line with
the safety local repair switch module for your application.
Figure C-4: Design with emergency stop 1-channel with monitored START
Number Order number Description
1 6ES7194-4GB10-0AA0 Module carrier, wide, 1 m
1 6ES7154-2AA00-0AB0 IM 154-2 DP interface module with terminating module
2 3RK1922-2BA00 Bus module
1 3RK1922-2BA01 Bus module for safety local repair switch module
1 3RK1304-0HS00-7AA0 Safety local repair switch module
1 3RK1304-0HS00-8AA0 400 V shutdown
1 3RK1304-5xS40-3AA0 RSe-HF motor starter
1)
2 3RK1922-2BQ00 Energy jumper plug
2 3RK1902-0CK00 Cap for energy bus
1 3RK1911-2BEx0 Connector set for energy supply
1)
1 3RK1902-0Cx00 Connector set for motor connection
1)
1 XXX Emergency stop switch; 1-pole, NC contact
1 XXX Switch for START; 1-pole, NO contact
1) x = according to model
Module carrier, wide (for motor starters)
Terminating module
ON
OFF
O
Interface
module
Safety local
repair switch
module
400 V shut-
down module
RSe
High feature