Device functions
SIMATIC - ET 200pro motor starters
GWA 4NEB 950 5661-02 DS 06
10-49
10.18.3 Plausibility check of data
Description
The motor starter checks all incoming parameters for validity and plausibility.
In the case of incorrect parameters
during a startup (after power ON) the messages ’Group fault’ and ’Incorrect
parameter value’ are set.
Motor and brake output remain switched off.
in ongoing operation, the messages ’Incorrect parameter value’ or ’Parame-
terization in ON status not permitted’ are set. ’Group fault’ is not set.
Motor and brake output are not switched off.
10.18.4 Output of messages
This device function delivers the following messages:
Messages Meaning
General messages
Ready (automatic) Device can be operated via host (e.g. PLC)
Group fault At least 1 fault is set.
General warning At least 1 warning exists
Process image fault Process image of the outputs contains
nonallowable bit combination, e.g. ’Motor
cw’ and ’Motor ccw’ set simultaneously
Field bus connection
Bus fault Device has no rear wall bus communica-
tion (ESSA3 interface to the controller
interrupted)
CPU/master STOP PLC program no longer being processed
Acknowledgement
Trip reset completed Trip teset accepted, i.e. fault has been
acknowledged.
Trip reset not possible Unable to acknowledge fault as the reason
for the shutdown is still present.
Operating type monitoring
Automatic operating mode Automatic (PLC control)
Manual bus operating mode Manual operation via field bus
(B&B control)
Manual local operating mode Manual operation via local device interface
(B&B control)
Lost connection in manual operating mode During manual operation, the associated
communication connection was inter-
rupted for longer than 5 seconds.
Table 10-32: Communication – Messages