Siemens SINAMICS G120 Operations Instructions Page 87

  • Download
  • Add to my manuals
  • Print
  • Page
    / 304
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 86
Commissioning
4.6 Data backup and standard commissioning
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
85
Inverter with enabled safety functions
You must confirm the settings of the safety functions.
Table 4- 3 Procedure
STARTER BOP-2
Set the following parameters:
p9761 = … Password for the safety functions
p0010 = 95 Changing the safety functions
p9701 = 220 Confirm the settings of the safety
functions
1. Go online with STARTER
2. Call the safety functions screen form
3. Click on the "Change settings" button
4. Enter the password for the safety functions
5. Click on the "Activate settings" button.
p0010 = 0 Exit change
Final steps:
1. Switch off the inverter supply voltage
2. Wait until all LEDs on the inverter go dark. Now switch on the inverter supply voltage
again. Your settings only become effective after this power-on reset.
4.6.1.3 Safely remove the memory card
CAUTION
The file system on the memory card can be destroyed if the memory card is removed while
the inverter is switched on without first requesting and confirming this using the "safe
removal" function. The memory card will then no longer function.
Procedure with STARTER or BOP-2:
1. Set p9400 to 2.
2. Check the value of parameter p9400.
If it is permissible to remove the memory card, p9400 is set to 3.
3. Remove the memory card.
Page view 86
1 2 ... 82 83 84 85 86 87 88 89 90 91 92 ... 303 304

Comments to this Manuals

No comments