Commissioning
4.1 Restoring the factory setting
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
57
4.1 Restoring the factory setting
There are cases where something goes wrong when commissioning a drive system e.g.:
The line voltage was interrupted during commissioning and you were not able to
complete commissioning.
You got confused when setting the parameters and you can no longer understand the
individual settings that you made.
You don't know whether the inverter was already operational
In cases such as these, reset the inverter to the factory settings.
Deactivating safety functions
The parameters of the safety functions can only be reset if you first deactivate the safety
functions.
Table 4- 1 Procedure
STARTER BOP-2
Set the following parameters:
p9761 = … Password for the safety functions
p0010 = 95 Changing the safety functions
p9601 = 0 Deactivate safety functions
p9700 = 208 Copy parameter
p9701 = 220 Confirm setting
1. Go online with STARTER
2. Call the safety functions screen form
3. Deactivate the safety functions
p0010 = 0 Exit change
Final steps:
1. Switch off the inverter supply voltage
2. Wait until all LEDs on the inverter go dark. Now switch on the inverter supply voltage
again. Your settings only become effective after this power-on reset.