Installing
3.3 Installing the Power Module
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
31
Dimensions and drilling patterns for the PM240 Power Modules
&RROLQJDLU
7KHUPDO
GLVVLSDWLRQ
:LGWK
+HLJKW
'HSWK
'HSWK
WRSERWWRP
ODWHUDO ODWHUDO
E
&
RQWURO8QLW
E
D
)6%)6)
)6$)6*;
)6$)6*;
)6$)6)
F
E
E
D
)6*;
F
D
)6$
F
Figure 3-1 PM240 drilling pattern
Table 3- 1 PM240, IP20 dimensions
Dimensions (mm) Clearances (mm)
Frame size
Height Width Depth a b c top bottom lateral
FSA 173 73 145 160 36.5 -- 100 100 30*
FSB 270 153 165 258 133 -- 100 100 40*
FSC 334 189 185 323 167 -- 125 125 50*
FSD without filter 419 275 204 325 235 11 300 300 0
FSD with filter, Class A 512 275 204 419 235 11 300 300 0
FSE without filter 499 275 204 405 235 11 300 300 0
FSE with filter, Class A 635 275 204 541 235 11 300 300 0
FSF without filter 634 350 316 598 300 11 350 350 0
FSF with filter, Class A 934 350 316 899 300 11 350 350 0
FSGX 1533 326 547 1506 125 14.5 250 150 50
Fixing: FSA/FSB: M4 screws, 2.5 Nm / 22 lbf .in
FSD/FSE: M6 screws, 6 Nm/53 lbf .in
FSC: M5 screws, 2.5 Nm / 22 lbf .in FSF/FSGX: M8
screws, 13 Nm / 115 lbf .in
*) up to 40 °C without any lateral clearance