Alarms, faults and system messages
9.4 List of alarms and faults
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
261
Number Cause Remedy
F30021 Ground fault
Check the power cable connections.
Check the motor.
Check the current transformer.
Check the cables and contacts of the brake connection (a wire might
be broken).
F30027 Time monitoring for DC link pre-
charging
Check the supply voltage at the input terminals.
Check the line voltage setting (p0210).
F30035 Overtemperature, intake air
F30036 Overtemperature, inside area
Check whether the fan is running.
Check the fan filter elements.
Check whether the ambient temperature is in the permissible range.
F30037 Rectifier overtemperature See F30035 and, in addition:
Check the motor load.
Check the line phases
A30049 Internal fan defective Check the internal fan and if required replace.
A30502 DC link overvoltage
Check the unit supply voltage (p0210).
Check the dimensioning of the line reactor.
A30920 Temperature sensor fault Check that the sensor is connected correctly.
F30059 Internal fan defective Check the internal fan and if required replace.
For further information, please refer to the List Manual.