Technical data
10.3 Technical data, Power Modules
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
267
Definitions
• LO input current
100 % of the permissible input current for a load cycle according to
Low Overload (LO base load input current).
• LO output current
100 % of the permissible output current for a load cycle according
to Low Overload (LO base load output current).
• LO power
Power of the inverter for LO output current.
• HO input current
100 % of the permissible input current for a load cycle according to
High Overload (HO base load input current).
• HO output current
100 % of the permissible output current for a load cycle according
to High Overload (HO base load output current).
• HO power
Power of the inverter for HO output current.
If the power data comprise rated values without any further specifications they always refer
to an overload capability corresponding to Low Overload.
NOTICE
UL-certified fuses must be used
In order that the system is in compliance with UL, UL certified fuses, circuit breakers or self-
protected combination motor controllers must be used.