Description
2.4 Reactors and filters
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
25
Frame size FSA FSB FSC FSD FSE FSF FSGX
PM240, 3AC 400V - power units with integrated braking chopper
1)
Power range (LO) in kW 0.37 … 1.5 2.2 … 4 7.5 … 15 18.5 … 30 37 … 45 55 … 132 160 … 250
line filter, Class A ○ ● ● ● ● ◑ ◑
PM250, 3AC 400V - power units capable of energy recovery
Power range (LO) in kW --- --- 7.5 … 15 18.5 … 30 37 … 45 55 … 90 ---
line filter, Class A --- --- ● ● ● ● ---
PM260, 3AC 690V - power units capable of energy recovery
Power range (LO) in kW --- --- --- 11 … 18.5 --- 30 … 55 ---
line filter, Class A --- --- --- ○/● --- ○/● ---
Sine-wave filter --- --- --- ● --- ● ---
○ = without; ● = integrated; ◑ = from 110 kW for external mounting
1) The Power Module PM240 FSGX is supplied without braking chopper, but is prepared for installation of an optional
braking chopper
2.4 Reactors and filters
Overview
Depending on the Power Module, the following combinations with filters and reactors are
permitted:
Line-side components Load-side components Power Module
Line reactor Line filters
class B
Braking
resistor
Sine-wave filter Output reactor
PM240 ● ● ● ● ●
PM250 - ● - ● ●
PM260 - ● - integrated -
For further details, refer to the connection example in section Procedure for installing the
freque
ncy inverter (Page 27).