Siemens SINAMICS G120 Operations Instructions Page 78

  • Download
  • Add to my manuals
  • Print
  • Page
    / 304
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 77
Commissioning
4.5 Commissioning with STARTER
Inverter with CU240B-2 and CU240E-2 Control Units
76 Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
Switch on motor for motor data identification
CAUTION
Motor data identification for dangerous loads
Secure dangerous plant and system parts before starting the motor data identification, e.g.
by fencing off the dangerous location or lowering a suspended load to the floor.
Open by double-clicking on the control panel
in STARTER.
Fetch the master control for the converter
Set the "Enable signals"
Switch on the motor.
The converter now starts to identify the motor
data. This measurement can take several
minutes. After the measurement the converter
switches off the motor.
Relinquish the master control after the motor
data identification.
Page view 77
1 2 ... 73 74 75 76 77 78 79 80 81 82 83 ... 303 304

Comments to this Manuals

No comments