Functions
7.10 Safe Torque Off (STO) safety function
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
229
7.10.7.4 Setting STO
You can adapt the STO function according to your requirements in the following screen.
Set the following in the above screen:
① ② F-DI input filter (debounce time) and monitoring for simultaneous operation
(discrepancy):
The method of functioning of the two filters is described in the section entitled F-DI
sign
al filtering (Page 223).
③ ④ Time in
terval for forced dormant error detection:
Information regarding forced dormant error detection can be found in the Forced
dorm
ant error detection (Page 226) section.
Close the screen.
7.10.7.5 Activate settings
Click "Copy parameters" and then click "Activate settings":
You are prompted to allocate a password if the password = 0 (factory setting).
If you try to set a password that is not permissible, the old password will not be changed.
Further information can be found in the section Password (Page 226).
Confirm the prompt for saving your settings (copy RAM to ROM).