Adapt terminal strip
5.3 Digital outputs
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
93
5.3 Digital outputs
Digital output terminals Changing the function of the digital output





'21&
'212
'2&20
'2326
'21(*
BO: ryyxx.n
p0731
p0730



'21&
'212
'2&20
p0732
Interconnect the digital output with a binector output of your
choice.
Binector outputs are marked with "BO" in the parameter list
of the List Manual.
1
Not available with CU240B-2 and CU240B-2 DP Control Units
Table 5- 3 Binector outputs of the inverter (selection)
0 Deactivating digital output r0052.9 Process data control
r0052.0 Drive ready r0052.10 f_actual >= p1082 (f_max)
r0052.1 Drive ready for operation r0052.11 Alarm: Motor current/torque limit
r0052.2 Drive running r0052.12 Brake active
r0052.3 Drive fault active r0052.13 Motor overload
r0052.4 OFF2 active r0052.14 Motor CW rotation
r0052.5 OFF3 active r0052.15 Inverter overload
r0052.6 Closing lockout active r0053.0 DC braking active
r0052.7 Drive alarm active r0053.2 f_actual > p1080 (f_min)
r0052.8 Setpoint/actual value discrepancy r0053.6 f_actual ≥ setpoint (f_setpoint)
A complete list of the binector outputs is provided in the List Manual.
Table 5- 4 Example:


'2
r0052.3 52.3
p0731
Signal fault via digital output 1.
Advanced settings
You can invert the signal of the digital output using parameter p0748.
For more information, see the parameter list and the function block diagrams 2230 ff of the
List Manual.