Configuring the fieldbus
6.1 Communication via PROFIBUS
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
103
6.1.2 Setting the address
You can set the inverter's PROFIBUS address using either DIP switches on the Control Unit
or parameter p0918.
Valid PROFIBUS addresses: 1 … 125
Invalid PROFIBUS addresses: 0, 126, 127
If you have specified a valid address using DIP switches, this address will always be the one
that takes effect and p0918 cannot be changed.
If you set all DIP switches to "OFF" (0) or "ON" (1), then p0918 defines the address.
The positions and settings of the DIP switches are described in Section: Interfaces,
c
onnectors, switches, terminal blocks and LEDs of the CU (Page 43).
CAUTION
A bus address that has been changed is only effective after the inverter has been switched
off and back on again.