Siemens SINAMICS G120 Operations Instructions Page 130

  • Download
  • Add to my manuals
  • Print
  • Page
    / 304
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 129
Configuring the fieldbus
6.2 Communication via RS485
Inverter with CU240B-2 and CU240E-2 Control Units
128 Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
The following table includes the request ID for telegrams between the master → inverter.
Table 6- 21 Request identifier (master → inverter)
Response identifier
Request
identifier
Description
Positive Negative
0 No request 0 7
1 Request parameter value 1 / 2 7
2 Change parameter value (word) 1 7
3 Change parameter value (double word) 2 7
4 Request descriptive element
1)
3 7
6 Request parameter value
1) 2)
4 / 5 7
7 Change parameter value (word)
1) 2)
4 7
8 Change parameter value (double word)
1) 2)
5 7
1) The required element of the parameter description is specified in IND (2nd word).
2) Identifier 1 is identical to identifier 6, ID 2 is identical to 7, and 3 is identical to 8. We recommend
that you use identifiers 6, 7, and 8.
The following table includes the response ID for telegrams between the inverter → master.
The response ID depends on the request ID.
Table 6- 22 Response identifier (inverter → master)
Response
identifier
Description
0 No response
1 Transfer parameter value (word)
2 Transfer parameter value (double word)
3 Transfer descriptive element
1)
4 Transfer parameter value (field, word)
2)
5 Transfer parameter value (field, double word)
2)
6 Transfer number of field elements
7 Request cannot be processed, task cannot be executed (with error number)
1) The required element of the parameter description is specified in IND (2nd word).
2) The required element of the indexed parameter is specified in IND (2nd word).