Siemens SINAMICS G120 Operations Instructions Page 35

  • Download
  • Add to my manuals
  • Print
  • Page
    / 304
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 34
Installing
3.3 Installing the Power Module
Inverter with CU240B-2 and CU240E-2 Control Units
Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
33
Dimensions and drilling patterns for the PM260 Power Modules
:LGWK
+HLJKW
'HSWK
WRSERWWRP
ODWHUDO ODWHUDO
'HSWK E
D
)6')6)
)6')6)
)6')6)
)6')6)
F
&RQWURO8QLW
Figure 3-3 PM260 drilling pattern
Table 3- 3 PM260, IP20 dimensions
Dimensions (mm) Clearances (mm) Frame size
Height Width Depth a b c top bottom lateral
FSD without / with filter 419 275 204 419 235 11 300 300 30*
FSF without / with filter 634 350 316 598 300 11 350 350 0
Fixing: FSD: M6 screws, 6 Nm/53 lbf.in FSF: M8 screws, 13 Nm / 115 lbf.in
*) up to 40 °C without any lateral clearance
Page view 34
1 2 ... 30 31 32 33 34 35 36 37 38 39 40 ... 303 304

Comments to this Manuals

No comments