Configuring the fieldbus
6.2 Communication via RS485
Inverter with CU240B-2 and CU240E-2 Control Units
134 Operating Instructions, 01/2011, FW 4.4, A5E02299792B AB
6.2.2.8 USS process data channel (PZD)
Description
Process data (PZD) is exchanged between the master and slave in this telegram range.
Depending on the direction of transfer, the process data channel contains request data for
the slave or response data to the master. The request contains control words and setpoints
for the slaves, while the response contains status words and actual values for the master.


67: +6: 67:
S
=6: +,: =6:
S 
S 
3=' 3=' 3=' 3=' 3='
3='
3=' 3=' 3=' 3='
5HVSRQVH
WR866PDVWHU
5HTXHVW
WR866VODYH
Figure 6-9 Process data channel
The number of PZD words in a USS telegram is defined by parameter p2022. The first two
words are:
Control 1 (STW1, r0054) and main setpoint (HSW)
Status word 1 (ZSW1, r0052) and main actual value (HIW)
If P2022 is greater than or the same as 4, the additional control word (STW2, r0055) is
transferred as the fourth PZD word (default setting).
You define the sources of the PZD using parameter p2051.
For further information, please refer to the Parameter Manual.
6.2.2.9 Time-out and other errors
You require the telegram runtimes in order to set the telegram monitoring. The character
runtime is the basis of the telegram runtime:
Table 6- 27 Character runtime
Baud rate in bit/s Transmission time per bit Character run time (= 11 bits)
9600 104.170 µs 1.146 ms
19200 52.084 µs 0.573 ms
38400 26.042 µs 0.286 ms
115200 5.340 µs 0.059 ms