Siemens Schweiz AG Basic units RVS61.843 and RVS41.813 CE1U2355en_02
Landis & Staefa Division The settings in detail 3. Juli 2008
The deviation of the actual room temperature from the setpoint is measured and taken
into account when controlling the temperature. In this way, account is taken of room
temperature deviations to facilitate more accurate room temperature control. The
authority of deviation is set as a percentage figure. The better the reference room
conditions (correct room temperature, correct mounting location, etc.) the higher the
value can be set.
Example:
Approx. 60% Good reference room conditions
Approx. 20% Unfavorable reference room
To activate the function, following must be considered:
A room sensor must be connected
The ”Room influence“ setting must be between 1 and 99
There should be no controlled valves in the reference room (mounting location of
the room sensor) (If such valves are installed, they must be set to their fully open
position)
The flow temperature is controlled depending on the room temperature setpoint, the
current room temperature and the progression of the room temperature. For example, a
slight increase of the room temperature causes an immediate drop of the flow
temperature.
To activate the function, following must be considered:
A room sensor must be connected
“Room influence“ must be set to 100%
There should be no controlled valves in the reference room (mounting location of
the room sensor) (If such valves are installed, they must be set to their fully open
position)
Room temperature limitation
Line no. Operating line
932 Room temperature limitation
The “Room temperature limitation” function makes it possible to deactivate the cooling
circuit pump if the room temperature falls by more than the preset difference below the
effective room temperature setpoint (with summer compensation, 920).
The heating circuit pump will be activated again as soon as the room temperature
returns to a level below the current room temperature setpoint.
During the time the “Room temperature limitation“ function is active, no cooling request
is sent to the source.
The function is deactivated in the following situations:
Room sensor not installed
“Room temperature limitation“ = ---
"Room influence“ (928) = --- (pure weather compensation)
ON
TRKw-SDR
2355Z10
TRKw
TRx
P
OFF
°C
TRx Actual value of the room
temperature
TRKw Room temperature setpoint
cooling
(incl.
summer compensation)
SDR Room’s switching differential
P Pump
t Time
Weather compensation
with room influence
Pure room compensation