Siemens Switzerland Basic units RVS61.843 and RVS41.813 CE1U2355en_02
HVAC Products Contents 3. Juli 2008
Function input
Hx
(5950, 6046,
5960)
Function
output QX..
State Hx Release status of source
-
x
x No heating
Swi’pool “Not"
pump Hx
x
No direct heating (Hx acts on
solar function)
Swi’pool
Pump Hx
Inactive Locked
Swi’pool
Pump Hx
Active Released
- = release of swimming pool not set
x = not relevant
Switch-on command HP stage 1 (heating only)
By closing a contact connected to this input (e.g. by an external controller or a
superposed building automation and control system), stage 1 of the heat pump is put
into operation. It remains in operation until contact Hx opens again or until the heat
pump is shut down by a safety function (e.g. due to high-pressure, low-pressure, or hot-
gas temperature).
Internal requests, DHW requests and requests via bus are suppressed. No
consideration is given to minimum off time and minimum running time. The prerun and
overrun times of the condenser pump and source pump are taken into account. Normal
defrost is possible.
Switch-on command HP stage 2 (heating only)
By closing a contact connected to this input (e.g. by an external controller or a
superposed building automation and control system), stage 2 of the heat pump is put
into operation. It remains in operation until contact Hx opens again or until the heat
pump is shut down by a safety function (e.g. due to high-pressure, low-pressure, or hot-
gas temperature).
Internal requests, DHW requests and requests via bus are suppressed. No
consideration is given to minimum off time and minimum running time. The prerun and
overrun times of the condenser pump and source pump are taken into account. Normal
defrost is possible.
NC contact
The contact is normally closed and must be opened to activate the selected Hx
function.
NO contact
The contact is normally open and must be closed to activate the selected function Hx.
The descriptions given on the functions of contact Hx refer to the setting as NO contact.
If input H1, H2, H3 (5950, 6046, 5960) is used as a contact input (”Min flow temp setp”
or “Refrigeration request”), the controller uses the value set here as the setpoint.
The heat pump is controlled constantly at the temperature level set here, either until
contact Hx opens again or until a higher heating / cooling request is delivered.
If several requests for heating or cooling are received at the same time (contact Hx,
DHW or from the controller itself), the highest or lowest of them is automatically
selected.
Example of minimum flow temperature setpoint:
Type of contact Hx
Function value contact Hx