Siemens Switzerland Basic units RVS61.843 and RVS41.813 CE1U2355en_02
HVAC Products Contents 3. Juli 2008
Speed-controlled pump
Line no. Operating line
5530 Pump speed min
The minimum speed of the pump for instantaneous DHW heater can be defined. It is
thus possible to negate the lowest pump speeds, which cannot be properly controlled
.
Mixing valve control
Line no. Operating line
5544 Actuator running time
Setting the running time of the actuator used with the mixing valve.
6.19 Configuration
Procedure
First, make use of the presetting choices and enter the plant diagram that comes
closest to the plant in question. Then, modify manually the individual partial diagrams to
match them to the actual requirements.
After that, select the extra functions and make the fine-tuning via the operating lines of
the individual parameters.
Preselection of
plant diagram
Line no. Operating line
5700 Preselection
The plant diagrams shown in chapter “Applications“ can be preselected by entering a
diagram number. The plant diagram is the result of preselection plus the connected
sensors.
The sensors contained in the selected plant diagram must be connected to ensure that
automatic sensor identification will not detect some other plant diagram.
Manual setting /
adjustment of partial diagrams
The plant diagrams consist of several partial diagrams.
The required partial diagrams can be used to manually produce the required final plant
diagram.
But it is also possible to modify and adjust partial diagrams of a plant diagram
generated via “Presetting” (5700).
A catalog with partial diagrams, which is separately available, contains the partial
diagrams implemented in the controller – classified according to groups. Also listed in
the catalog are the required operating lines which must be set to produce the
respective partial diagrams, plus the sensors required for the relevant partial diagram.
On operating lines 6212 through 6217 (see page 175), you can check whether the
adjustments led to the right partial diagram. The check number shown there must
accord with the relevant components group.
Pump speed min
A
ctuator running time
Preselection
Only RVS61..
Only RVS61..