Siemens Albatros2 AVS37 User Manual Page 136

  • Download
  • Add to my manuals
  • Print
  • Page
    / 235
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 135
136/235
Siemens Switzerland Basic units RVS61.843 and RVS41.813 CE1U2355en_02
HVAC Products Contents 3. Juli 2008
Priority
Line no. Operating line
3822 Charging prio storage tank
None
DHW storage tank
Buffer sensor
3825 Charging time relative prio
3826 Waiting time relative prio
3827 Waiting time parallel op
3828 Delay secondary pump
The priority circuit for the swimming pool (2065) can impact the storage tank priority of
solar charging and possibly charge the swimming pool before charging the storage
tanks.
If a plant uses several heat exchangers, it is possible to set a priority for the integrated
storage tanks, which defines the charging sequence.
None
Every storage tank is charged alternately for a temperature increase of 5 °C at a time,
until every setpoint of level A, B or C (see below) is reached. The setpoints of the next
higher level are approached only when all setpoints of the previous level have been
reached.
DHW storage tank
During solar charging, preference is given to the DHW storage tank. At every level A, B
or C (see below), it is charged with priority. Only then will the other consumers of the
same level be charged. As soon as all setpoints of a level are attained, those of the
next level are approached, whereby priority is again given to the DHW storage tank.
Buffer sensor
During solar charging, preference is given to the buffer storage tank. At every level A, B
or C (see below), it is charged with priority. Only then will the other consumers of the
same level be charged. As soon as all setpoints of a level are attained, those of the
next level are approached, whereby priority is again given to the buffer storage tank.
Storage tank setpoints:
Level DHW storage tank Buffer sensor Swimming pool
(1)
A 1610 Nominal setpoint Puffersollwert (Schleppzeiger) 2055 Setpoint solar heating
B
5050 Charging temperature
max
4750 Charging temperature
max
2055 Setpoint solar heating
C
5051 Storage tank temp
max
4751 Storage tank temp max
2070 Swimming pool temp
max
(1)
When priority for the swimming pool is activated (2065), the swimming pool is
charged before the storage tanks.
If the preferred storage tank cannot be charged in accordance with charging control,
priority is transferred to the next storage tank or the swimming pool for the period of
time set (e.g. temperature differential between collector and storage tank too great).
As soon as the preferred storage tank (according to setting "Charging prio storage
tank") is again ready to be charged, the transfer of priority will immediately be stopped.
Charging prio storage tank
Charging time relative prio