Siemens Schweiz AG Basic units RVS61.843 and RVS41.813 CE1U2355en_02
Landis & Staefa Division The settings in detail 3. Juli 2008
ECO
Line no. Operating line
912 Cooling limit at OT
913 Lock time at end of heating
If the composite outside temperature lies above the cooling limit, cooling is released;
cooling is locked when the outside temperature drops to at least 0.5 °C below the
cooling limit.
To avoid too rapid a change to cooling at the end of the heating phase, the cooling
function is disabled for the period of time which can be set here. This locking period
begins when there is no heating request from heating circuit 1. Heating requests from
heating circuit 2 or heating circuit P are not taken into consideration.
The locking time is aborted by switching the operating mode button off and on again.
Summer compensation
Line no. Operating line
918 Summer comp start at OT
919 Summer comp end at OT
920 Summer comp setp increase
In summer, the cooling Comfort setpoint (902) is shifted upwards as the outside
temperature increases. This saves cooling energy, and prevents too great a differential
between the room and the outside temperature.
The resulting room temperature setpoint (cooling) can be displayed on the info level.
Summer compensation starts to take effect at the outside temperature set here. If the
outside temperature continues to rise, the Comfort setpoint is raised continuously.
Summer compensation takes full effect at this outside temperature (920). The Comfort
setpoint is not affected by any further increase in the outside temperature.
This setting determines the maximum permissible increase in the Comfort setpoint.
TKw
920
919
TA
2355Z05
918
902
TKw Comfort setpoint
TA Outside temperature
Cooling limit at OT
Lock time at end of
heating
Summer comp start at OT
Summer comp end at OT
Summer comp setp
increase