Siemens Switzerland Basic units RVS61.843 and RVS41.813 CE1U2355en_02
HVAC Products Contents 3. Juli 2008
Release
Line no. Operating line
907 Release
24 h/day ¦ Time program heating circuit ¦ Time program 5
Parameter "Release" determines the time program in accordance with which cooling is
enabled.
Cooling is permanently enabled (24 hours a day)
Cooling is enabled in accordance with the heating circuit’s time program
Release of cooling takes place in accordance with time program 5.
Cooling curve
Line no. Operating line
908 Flow setp at OT 25°C
909 Flow setp at OT 35°C
The controller determines the required flow temperature at a certain composite outside
temperature. The cooling curve is determined by defining 2 fixed points (flow
temperature setpoint at 25 °C and 35 °C).
This determines the flow temperature required for cooling at a composite outside
temperature of 25 °C without giving consideration to summer compensation.
This determines the flow temperature required for cooling at a composite outside
temperature of 35 °C without giving consideration to summer compensation.
TVKw Flow temperature setpoint for cooling
Tagem Composite outside temperature
The set cooling curve is based on a room temperature setpoint of 25 °C. If the room
temperature setpoint is changed, the cooling curve automatically adapts to the new
value.
24 hours a day
Time program HC
Time program 5
Flow setp at OT 25°C
Flow setp at OT 35°C
TVKw
35°C
TAgem
2355Z06
25°C
909
908