Siemens Switzerland Basic units RVS61.843 and RVS41.813 CE1U2355en_02
HVAC Products Contents 3. Juli 2008
If the value is above setting “HP interval“ (7070), symbol appears on the display and
a maintenance message on the info level:
17: HP interval (priority 6)
This parameter can be reset, provided the respective access right is granted.
Maximum number of starts of compressor 1 per hour run
Setting the maximum permissible number of starts of compressor 1 per hour run.
Average number of starts of compressor 1 per hour run, reached over the last 6 weeks.
If the value lies above setting “Max starts compr1/hrs run“ (7072), symbol
appears
on the display and a maintenance message on the info level:
8: Too many starts compr 1 (priority 9)
This parameter can be reset, provided the respective access right is granted.
Maximum number of starts of compressor 2 per hour run
Setting the maximum permissible number of starts of compressor 2 per hour run.
Average number of starts of compressor 2 per hour run, reached over the last 6 weeks.
If the value is above setting “Max starts compr2/hrs run“ (7074), symbol
appears on
the display and a maintenance message on the info level:
9: Too many starts compr 2 (priority 9)
This parameter can be reset, provided the respective access right is granted.
Number of times per week the temperature differential across the condenser
exceeds the maximum
Setting the number of times within a 7-day period the maximum temperature differential
across the condenser may be exceeded.
Number of times the maximum temperature differential across the condenser was
exceeded within a 7-day period. If the value is above setting “Diff condens max/week“
(7076), symbol
appears on the display and a maintenance message on the info
level:
13: Diff condens max (priority 3)
This parameter can be reset, provided the respective access right is granted.
Number of times per week the temperature differential across the condenser falls
below the minimum
Indicates how many times the temperature differential across the condenser may drop
below the minimum within a 7-day period.
Number of times the temperature differential across the condenser dropped below the
minimum within a 7-day period. If the value is above setting “Diff condens min/week“
(7078), symbol
appears on the display and a maintenance message on the info
level:
14: Diff condens min (priority 3)
This parameter can be reset, provided the respective access right is granted.
Number of times per week the temperature differential across the evaporator
exceeds the maximum
Reset
Max starts compr1/hrs run
Cur starts compr1/hrs run
Reset
Max starts compr2/hrs run
Curr starts comp2/hrs run
Reset
Diff condens max/week
Cur diff condens
max/week
Reset
Diff condens min/week
Cur diff condens min/week
Reset