Siemens Albatros2 AVS37 User Manual Page 118

  • Download
  • Add to my manuals
  • Print
  • Page
    / 235
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 117
118/235
Siemens Switzerland Basic units RVS61.843 and RVS41.813 CE1U2355en_02
HVAC Products Contents 3. Juli 2008
SD
Tx
Tw
0
S1
1
0
S2
1
2864
T
t
TW Flow or return temperature setpoint
Tx Actual value of flow or return
temperature
SD Switching differential
S1 Heat pump stage 1
S2 Heat pump stage 2
2864 Reset integral stage 2
t Temperature
t Time
If both stages together deliver too much heat, the second stage is immediately switched
off when the switch-off point or, latest, the reduced maximum switch-off temperature is
reached (2844 and 2845).
Automatic changeover of the compressors ensures that both compressors operate
pretty much the same number of hours.
If the difference of operating hours between the first and the second compressor
exceeds the limit (h) set here, the order of startup changes as soon as both
compressors are switched off. This means that compressor 1 becomes compressor 2,
and vice versa. The current compressor sequence appears on operating line 8446.
Electric immersion heater in the flow
Relays K25 and K26 are intended for using an electric immersion heater in the flow.
They are controlled by 2 appropriately configured multifunctional relay outputs QX1 –
QX6.
If both relays are present, the electric immersion heater is controlled in 3 stages (1st
stage K25, 2nd stage K26, and 3rd stage K25 and K26).
If a flow temperature sensor (B21) is connected, it is used for control to the flow
temperature setpoint. The switching differential is 1 °C.
If the flow temperature sensor is missing, but a common flow temperature sensor (B10)
is available, that sensor is used for conrol.
If no flow temperature sensor is present, the electric immersion heater is controlled
based on the return temperature (B71) and the return temperature setpoint. The
switching differential is set with parameter “Switching diff return temp” (2840).
Line no. Operating line
2880 Use electric flow
2881 Locking time electric flow
2882 Release integr electric flow
2883 Reset integr electric flow
2884 Release el flow below OT
Control of the electric immersion heater is dependent on the selected kind of use.
Substitute
The electric immersion heater is only used in emergency operation (7141 and 7142).
When activating emergency operation (manually or automatically), the electric
immersion heater is immediately released to ensure control to the current setpoint. No
consideration is given to “Locking time electric flow” (2881) and to “Release electric
flow below OT” (2884).
If there is no control sensor (B21, B10, B71), the electric immersion heater is switched
on in emergency operation when there is a valid temperature request. In the case of a
Compr sequence
changeover
Use electric flow