Siemens Albatros2 AVS37 User Manual Page 105

  • Download
  • Add to my manuals
  • Print
  • Page
    / 235
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 104
105/235
Siemens Schweiz AG Basic units RVS61.843 and RVS41.813 CE1U2355en_02
Landis & Staefa Division The settings in detail 3. Juli 2008
Plants without buffer or combi storage tanks: Parameter “Charging priority“ should be
set to “Absolute“, ensuring that the consumers will be switched off. If this is not
observed, the required DHW temperature might not be reached.
Plants with buffer or combi storage tanks: Parameter “Charging priority“ should be set
to “None“. If this is not observed, the heating circuits of plants using storage tanks will
be unnecessarily restricted.
Parameter “Charging priority“ has no impact on the condenser pump Q9.
Legionella function
Line no. Operating line
1640 Legionella function
Off
Periodically
Fixed weekday
1641 Legionella funct periodically
1642 Legionella funct weekday
Monday…Sunday
1644 Legionella func time
1645 Legionella func setpoint
1646 Legionella funct duration
1647 Legionella funct circ pump
Periodically
The legionella function is repeated according to the interval set (1641). If the legionella
setpoint is attained via solar plant, independent of the time set, the period of time will be
started again.
Fixed weekday
The legionella function can be activated on a fixed weekday (1642). When using this
setting, heating up to the legionella setpoint takes place on the selected weekday,
independent of previous storage tank temperatures.
During the period of time the legionella function is performed, the DHW circulating
pump can be activated.
During the period of time the legionella function is carried out, there is a risk of scalding
when opening the taps.
Legionella function
Legionella funct circ pump
Page view 104
1 2 ... 100 101 102 103 104 105 106 107 108 109 110 ... 234 235

Comments to this Manuals

No comments