Plants without buffer or combi storage tanks: Parameter “Charging priority“ should be
set to “Absolute“, ensuring that the consumers will be switched off. If this is not
observed, the required DHW temperature might not be reached.
Plants with buffer or combi storage tanks: Parameter “Charging priority“ should be set
to “None“. If this is not observed, the heating circuits of plants using storage tanks will
be unnecessarily restricted.
Parameter “Charging priority“ has no impact on the condenser pump Q9.
Legionella function
Line no. Operating line
1640 Legionella function
Off
Periodically
Fixed weekday
1641 Legionella funct periodically
1642 Legionella funct weekday
Monday…Sunday
1644 Legionella func time
1645 Legionella func setpoint
1646 Legionella funct duration
1647 Legionella funct circ pump
• Periodically
The legionella function is repeated according to the interval set (1641). If the legionella
setpoint is attained via solar plant, independent of the time set, the period of time will be
started again.
• Fixed weekday
The legionella function can be activated on a fixed weekday (1642). When using this
setting, heating up to the legionella setpoint takes place on the selected weekday,
independent of previous storage tank temperatures.
During the period of time the legionella function is performed, the DHW circulating
pump can be activated.
During the period of time the legionella function is carried out, there is a risk of scalding
when opening the taps.
Legionella function
Legionella funct circ pump