Siemens Schweiz AG Basic units RVS61.843 and RVS41.813 CE1U2355en_02
Landis & Staefa Division The settings in detail 3. Juli 2008
Optimum start / stop control is possible with or without room temperature sensor.
Xein Switch-on time shifted forward in time
Xaus Switch-off time shifted forward in time
ZSP Time program
TRx Actual value of the room temperature
TRw Room temperature setpoint
Raising the Reduced setpoint
Line no. Operating line
HC1 HC2 HCP
800 1100 1400 Reduced setpoint increase start
801 1101 1401 Reduced setpoint increase end
The function is used primarily in connection with heating systems with only little spare
capacity (e.g. low-energy houses). In such cases, the heating up time at low outside
temperatures would be too long. When the Reduced setpoint is raised, the rooms are
prevented from cooling down excessively, thus shortening the heating up time when
changing to the nominal setpoint.
2358Z06
-15
-5
TR
TRK
TAgem
TRwA2TRwA1
TRR
TRwA1 Reduced setpoint increase start
TRwA2 Reduced setpoint increase end
TRK Comfort setpoint
TRR Reduced room temperature setpoint
Tagem Composite outside temperature
Overtemp prot pump heating circuit
Line no. Operating line
HC1 HC2 HCP
820 1120 1420 Overtemp prot pump heating circuit
In the case of heating plants with pump heating circuits, the flow temperature of the
heating circuit can be higher than the flow temperature called for by the heating curve,
the reason being higher requests from other heat consumers (mixing heating circuit,
DHW charging, external heat demand), or a parameterized minimum heat source
temperature. As a result of this too high flow temperature, the pump heating circuit
would assume excessive temperatures.
Function "Overtemperature protection for pump circuits" ensures that the energy supply
for pump heating circuits corresponds to the demand from the heating curve by
activating / deactivating the pump.
0
24
2358Z02
Xein Xaus
TRx
TRw
ZSP
1/4 °C