Siemens Switzerland Basic units RVS61.843 and RVS41.813 CE1U2355en_02
HVAC Products Contents 3. Juli 2008
Line no.
Operating line
5890
5891
5892
5894
5895
5896
5897
5898
Relay output QX1, QX2, QX3, QX4, QX5, QX6, QX7, QX8
None
Process reversing valve Y22
Hot-gas temp K31
El imm heater 1 flow K25
El imm heater 2 flow K26
Diverting valve cool strat2 Y28
System pump Q14
Cascade pump Q25
Heat generator shutoff valve Y4
El immersion heater DHW
Circulating pump Q4
Collector pump Q5
Solar pump external exchanger K9
Solar controlling element buffer K8
Solar controlling element swimming pool K18
Electric immersion heater buffer K16
H1 pump Q15
H2 pump Q18
H3 pump Q19
Heat circ pump HCP Q20
Diverting valve cooling Y21
Air dehumidifier K29
Heat request K27
Refrigeration request K28
Alarm output K10
Time program 5 K13
Heating circuit pump HC1 Q2
DHW controlling element Q3
Source pump Q8 / fan K19
Condenser pump Q9
Compressor stage 1 K1
Supplementary source control K32
Depending on the selection made, setting of the relay outputs assigns appropriate extra
functions to the basic diagrams. For detailed information, refer to section “Application
diagrams“.
None
The relay output cannot be assigned any function. The relay is inactive.
Compressor stage 2 K2
Relay is used for the control of a second compressor (refer to compressor 2)
Process reversing valve Y22
Control of process reversing valve Y22. The process reversing valve is required for
changeover from heating to cooling mode and for the heat pump’s defrost function.
Hot-gas temp K31
The relay is energized when a connected hot-gas temperature sensor B81 or B82
exceeds “Setpoint hot-gas temp” (2849), and deenergized, when the temperature drops
by the switching differential (2850) below the setpoint. The type of contact (2851) can
be selected.
Electric immersion heater flow K25
The relay is used for the control of an electric immersion heater in the flow (K25) or, in
the case of a 2-stage electric immersion heater, for control of the first stage.
Electric immersion heater flow K26
The relay is used for the control of the second stage of an electric immersion heater in
the flow (K26).
Relay outputs QX…
Only RVS41..