Siemens Switzerland Basic units RVS61.843 and RVS41.813 CE1U2355en_02
HVAC Products Contents 3. Juli 2008
Flow temperature setpoint limitations
Line no. Operating line
923 Flow temp setp min at OT 25°C
924 Flow temp setp min at OT 35°C
A low limit can be defined for the flow temperature required for cooling.
The limit curve is determined by defining 2 fixed points.
There is also a low limit for the resulting flow temperature setpoint, which must not fall
below 5 °C.
This determines the lowest permissible flow temperature at a composite outside
temperature of 25 °C.
This determines the lowest permissible flow temperature at a composite outside
temperature of 35 °C.
If there is no valid outside temperature available, the controller uses the value
"Flow temp setp min OT = 35 °C".
TVKw
35°C
TAgem
2355Z07
25°C
924
923
TVKw
TVKw_unb
TVKw Flow temperature setpoint for cooling (with minimum limitation)
TVKw_unb Flow temperature setpoint for cooling (without minimum limitation)
Tagem Composite outside temperature
Room influence
Line no. Operating line
928 Room influence
When using a room temperature sensor, there is a choice of 3 different types of
compensation.
Setting Type of compensation
% Pure weather compensation *
1…99% Weather compensation with room
influence *
100% Pure room compensation
* Outside sensor required.
The flow temperature is calculated with the help of the cooling curve as a function of
the composite outside temperature.
This type of compensation demands a correct adjustment of the cooling curve since in
that case the control gives no consideration to the room temperature.
Flow temp setp min at OT
25°C
Flow temp setp min at OT
35°C
Types of compensation
Pure weather
compensation