11 Alarms 09.91
11.6 Alarm list POWER ON
Scan:
Explanation:
Remedy:
5
Too many inp. buffer param.
When formatting user program memory with ”FORMAT USER M. ”
softkey.
The input buffer parameters (MIB parameters) require so much space
in the user memory that the user program memory is now less than 13
Kbytes.
Correct MD 5 (enter lower value) and reformat user program memory.
Scan:
Effect:
Explanation:
Remedy:
7
EPROM error
• Cyclically
• NC START disabled
• Output of setpoint 0
• NC Ready 2 (NCBB2) cancelled
• Servo enable cancelled after time in MD 156
has elapsed (servo enable relays drop out)
• An error was detected while verifying the
check sums.
• After switching the control off and on, the screen displays
which EPROM submodule is defective (see also Section
4.2.2)
Scan:
Effect:
Explanation:
Remedy:
8
Wrong axis/spindle assign.
• After modifying MD
• NC START disabled
• Output of setpoint 0
• NC Ready 2 (NCBB2) cancelled
Illegal assignment entered in MD 200* or MD 400* or MD 461*.
(e. g. measuring circuit has been assigned to a fictitious axis)
(See Section 8).
11–8 © Siemens AG 1990 All Rights Reserved 6ZB5 410-0DL02
SINUMERIK 810 GA3/820 GA3 (IA)