11 Alarms 11.90
11.11 Alarm list ACKNOWLEDGE
6134
Illegal block MC 5 program
Effect:
Remedy:
PLC STOP
PLC OVERALL RESET, reload PLC program
6135
Illegal block MC 5 data
Effect:
Remedy:
PLC STOP
PLC OVERALL RESET, reload PLC program
6136
Sumcheck error MC 5 block
Effect:
Remedy:
PLC STOP
PLC OVERALL RESET, reload PLC program
6137
Sumcheck error basic program
Effect:
Remedy:
PLC STOP
Replace system software
6138
No response from EU
Cause:
Effect:
Explanation:
Remedy:
No operating voltage at EU
Cable to EU not connected or defective
POWER ON : PLC STOP, control ramps up automatically after
fault has been rectified
Cyclic : PLC STOP, as a function of PLC-MD 2003 bit 2
May also occur in the event of major interference
Check cable, address setting EU No. = 0; +24V supply
voltage OK?
11–56 © Siemens AG 1990 All Rights Reserved 6ZB5 410-0DL02