Voice board IAV6-90
39
Building Technologies
Fire Safety & Security Products
6.3.2.2 Call-back
In order to activate this mode, option 5 at P183E must be OFF and option 8 at P175E 2E must be ON.
Dialer B options
P175E 2E 8
After reporting the event to the CMS the Control Panel rings off.
When this option is turned on, the Control Panel will ring off after reporting to the
CMS. The operator at CMS can then call the Control Panel during a period
10 minutes. The panel will answer the incoming call on the first ring.
If the DTMF code defined by parameter P175E 14E (as described above) is not
entered within 30 seconds, the panel will ring off. The panel will still answer any
new calls on the first ring within the 10 minutes after the original alarm was
transmitted. As soon as the panel receives the correct DTMF acknowledge code
the auto-answer feature (answering on the 1st ring) will be reset.
After the Control Panel has answered an incoming call, a short beep will sound at intervals of
5 seconds for a period of 30 seconds. If nothing happens and the 30 seconds timer expires, the panel
will ring off. If however the DTMF code programmed by parameter P175E 14E is entered before the
30 seconds timer has expired (for example if a code "1234" was programmed by parameter
P175E 14E, then the operator must enter 1-2-3-4-# at their telephone), the call will be extended. The
short beeps will stop and the two-way voice channel will remain open for 3 minutes (if no code has
been programmed at P175E 14E, the call can be extended by pressing the # button). After 2 minutes
and 30 seconds the short beeps will start again. The operator must repeat the above process to keep
the panel on-line for a further 3 minutes, otherwise the panel will ring off when the 3 minutes are over.
If the operator wishes to terminate the two-way voice connection, he should enter
0-0-0-# on his telephone which will tell the panel to ring off.
6.3.3 Additional commands available for Voice Board
6.3.3.1 Output DTMF
Output DTMF
P175E 12E 0-9999E
(Value 1-4 digit code 0-9999)
The panel can be configured to allow remote operation of the outputs via a remote
telephone. The code programmed at this address is the DTMF code that must be
used when performing this function. When dialing the panel and it has answered
the call, after waiting for the panel modem tones to stop you can enter in the 4 digit
DTMF code plus the output number you wish to control, e.g. 1 for output # 1, and
the current status will be given of the output associated with the code entered.
After that, if you press the <*> button on the telephone the status of the output will
toggle e.g. if it was previously on it will change to off or vice versa. When finished
you simply hang-up and 15 seconds later the panel will release the line.