System overview
19
Building Technologies
Fire Safety & Security Products
General Specifications:
z The range of the 12 V uut which is used for feeding sensors is between 10.2 to
14 V DC (working on mains or standby battery).Ripple is up to 0.1 V p.p.
z Each voltage out 12 V protected by reset able fuse of 500 mA.
z The max total current allowed to draw during alarm is 1 A.
z Self current consumption (IC60M+IKP6) from battery is: 100 mA.
z Operating temperature: 0-50º C
z Max. current consumption from the mains less than 150 mA.
z The panel is equipped with a type A power supply according EN 50131-6
To meet the EN 50131 and the T014 (Belgium) to withstand battery life not less of 12 hours please
note that the maximum current for accessories in standby mode should be less then 300 mA
AC Connections:
Connect the mains wires Phase (~) and Neutral (N) to the Mains terminal inside the
IC60M housing and secure the cable with the provided cable clamp
The AC Input is protected by fuse:
Fuse (TD-Time Delay) T250 mA/250 V, 5x20 mm Glass.
AC level 230 V, 50 Hz ±10%.
Notifications:
z Alarm transmission classification ATS 2
z According EN 50131-1 notification option A applies. This means that an external
warning device needs to be connected.
This panel is designed in accordance with:
z EN 50131-1
z TS 50131-3
z EN 50130-4
z EN 50130-5
z EN 50131-6
z EN 50131-5-3
z EN 50136-1-1
z EN 50136-2-1