System overview
18
Building Technologies
Fire Safety & Security Products
4 System overview
4.1 Sintony 60M modular
Outputs
Gnd Gnd
Gnd
Gnd12V 12V
12V
12V
1152263374CCCC48Tmp
AC_IN
C NC N
Relay/OUT4
COM
GND
IC-60M
In factory settings the
jumper is set between
COM & GND.
The com contact can be
connected to 12V by
setting the jumper.
With out the jumper the
relay contacts are floating.
Red
Black
OUTPUTS
INPUTS Z1...Z16 POWER FOR
DETECTORS &
CCESORIES
Out
TELECOM
LinIn
Dat
Lin
Clk
Neg
Pos
PHONE LINE IN
PHONE LINE IN
PHONE LINE OUT
BUS CONNECTION
FOR EXTERNAL
KEYPAD AND OTHER
ACCESSORIES
Fig. 1 Connection Diagram
The wiring option shown here with a common tamper input (TAMP/GND) is not
allowed in all countries, if the installation has to be done according to legal
requirements (e.g. Belgium/INCERT).To integrate the tamper contact directly into
each zone input, see also chapter
4.3.2: Zone wiring examples.
Battery Specifications for Model IC60 M
z Sealed Lead-Acid Rechargeable Battery 12 V/1.3 Ah up to 12 V/7 Ah
z Battery cutoff level (when AC mains fails): 10.3 V ± 0.1 V DC.
z Full charge after 48 hours.
z The current limit over charge is 600 mA.
Battery Connections
Connect a sealed lead acid rechargeable 12 V DC battery to the terminals labeled
red and black on the control panel being careful to observe the correct polarity. The
maximum recommended battery capacity is 7 amp hours. Battery charge current at
these terminals is limited to 600 mA maximum. The battery connection is protected
against short circuits by a thermal fuse (F1). The panel performs a dynamic load
test on the battery every 15 seconds and if it fails the test at any time it will flash
the battery LED.