SIA Codes reporting format SIA III
140
Building Technologies
Fire Safety & Security Products
25.2 Individual SIA reporting codes
You can also choose and set for every input zone and alarm event a individual
programming to the related type of report code.
Zone Alarm SIA Code
P196E 1-16E 1-14E
Each Input zone can be mapped to a special type of reporting. E.g. if zone 5 would
be equipped with a smoke detector instead of being used as a standard burglary
zone for intrusion the zone reporting should be changed to P196E 5E 4E. This
would change the reporting according to the enclosed table.
Miscellaneous SIA Codes
P197E 1-3E 1-14E
The general SIA reporting for the control panel of the 3 functions Panic, Fire
Medical can also be changed in the programming for individual settings according
to the enclosed table.
Event Description
Type
Program
Number
Alarm Restore Bypass
Un-
Bypass
Trouble
Trouble
Restore
Near
Alarm
Verified
Alarm
Burglary
1
BA BH BB BU BT BJ BA BV
Un-typed Alarm
2
UA UH UB UU UT UJ - -
Hold-up
3
HA HH HB HU HT HJ - -
Fire
4
FA FH FB FU FT FJ FA FM
Medical
5
MA MH MB MU MT MJ - -
Panic
6
PA PH PB PU PT PJ - -
Emergency
7
QA QH QB QU QT QJ - -
Gas
8
GA GH GB GU GT GJ - -
Sprinkler
9
SA SH SB SU ST SJ - -
Water
10
WA WH WB WU WT WJ - -
Heat
11
KA KH KB KU KT KJ - -
Freeze
12
ZA ZH ZB ZU ZT ZJ - -
Equipment
13
IA IR - - - - - -
Equip. Tamper
14
TA TH TB TU TT TJ - -
Tab. 9 Chart for the individual programmable SIA code events