Siemens SITRANS LR 300 Instruction Manual Page 58

  • Download
  • Add to my manuals
  • Print
  • Page
    / 140
  • Table of contents
  • TROUBLESHOOTING
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 57
Page 56 SITRANS LR 300 – INSTRUCTION MANUAL 7ML19985CL02
mmmmm
Parameters
Quick Start Parameters (P001 to P007)
Parameters P001 to P007 are the main settings that apply to all applications and make the
system operational.
P001 Operation (F = 3)
Sets the display variable for the local LCD only. (The primary variable for the HART/
Profibus Master is controlled by P201.)
P002 Material
Identifies the material being monitored.
P003 Measurement Response (F = 2)
Sets the reaction speed of the unit to the measurement changes in the target range.
Set P003 to a measurement response just faster than the maximum filling or emptying
rate (whichever is greater).
If the SITRANS LR 300 does not keep step with the rate of level change, select a faster
rate. If the reading bounces around an average value, select a slower rate. In general,
Values
1 Level: material level referenced to empty distance (P006)
2 Space: space to material level referenced from span (P007)
3 Distance: distance to target referenced from the flange face
Values
1 Liquids or slurries
Values
Mea suremen t Respon se
P700/P701
Echo Verification
P711
Fail-Safe Timer
P070
1 0.1m/minute slow 2 100
2 1m/minute 2 10
310m/minute 2 1
4100m/minute 0 0.1
5 1000m/minute fast 0 0
Level
(P001 = 1)
Space (a.k.a. ullage)
(P001 = 2)
Distance
(P001 = 3)
Note: P050 sets the SITRANS LR 300 to calculate readings based on reservoir
SITRANS LR 300.book Page 56 Monday, June 10, 2002 7:18 PM
Page view 57
1 2 ... 53 54 55 56 57 58 59 60 61 62 63 ... 139 140

Comments to this Manuals