Page 130 SITRANS LR 300 – INSTRUCTION MANUAL 7ML19985CL02
mmmmm
Appendix VII
Function Block 2 - Space
The second analog input function block produces the Space value. This is the same layout
as AI 1, but the internal parameters reference primary index 2 for all internal parameters.
(Example: index [1,1], [1,2] becomes [2,1] and [2,2].)
11 PV_SCALE PAR_PROFI_FB_PV_EU index [1,2]
PAR_PROFI_FB_PV_EU index [1,1]
Scaled to percent Array, float
12 OUT_SCALE PAR_PROFI_FB_SCALE_EU index[1,2]
PAR_PROFI_FB_SCALE_EU index[1,1]
PAR_PROFI_FB_SCALE_UNITS index[1,1]
PAR_PROFI_FB_SCALE_DECIMALS
index[1,1]
Scaling values record Record
Not
Used
13 LIN_TYPE This does not conform to
Profile 3.0 Class B
Uint8
14 CHANNEL Always mapped to TB1 Secondary Value 3 Map to TB (always 1) Uint16
Not
Used
15
16 PV_FTIME PAR_PROFI_FB_PVTIME –index [1,1] Filter time Float
17 FSAFE_TYPE PAR_PROFI_FB_FAILSAFE_TYPE –index [1,1] Uint8
18 FSAFE_VALUE PAR_PROFI_FB_FAILSAFE_VALUE –index
[1,1]
Float
19 ALARM_HYS PAR_PROFI_FB_ALARM_LIMITS – index
[1,1]
Float
21 HI_HI_LIM PAR_PROFI_FB_ALARM_LIMITS – index
[1,2]
Float
23 HI_LIM PAR_PROFI_FB_ALARM_LIMITS – index
[1,3]
Float
25 LO_LIM PAR_PROFI_FB_ALARM_LIMITS – index
[1,4]
Float
Not
Used
26
27 LO_LO_LIM PAR_PROFI_FB_ALARM_LIMITS – index
[1,5]
Float
Not
Used
30 HI_HI_ALM Record
Not
Used
31 HI_ALM Record
Not
Used
32 LO_ALM record
Not
Used
33 LO_LO_ALM Record
34 SIMULATE Not stored. Out of reset, simulation is always
disabled.
Simulation value, status
and state
Record
Not
Used
35 OUT_UNITS_TEXT String
Relative
Index
Name Number Description
Data Type &
size
SITRANS LR 300.book Page 130 Monday, June 10, 2002 7:18 PM