Start Up
Resetting a Parameter to Factory Setting
Accessing RUN Mode
Quick Start Programming
1. Configure all parameters to their factory settings by performing a master reset via
Parameter 999 (see page 82).
2. Set the following parameters for a Quick Start: (see page 56).
Numerous other program parameters can be changed subsequently, or during another
programming session. Please see Parameter Descriptions, starting on page 55, for a list
of available parameters.
3. After you have completed programming, press the PROGRAM key to return to
RUN mode.
1. Scroll to the parameter or enter its
address.
2. Press the CANCEL key
. The value
field goes blank and the EDIT icon
appears.
3. Press the ENTER
key
. The value
returns to factory default and the EDIT
icon disappears.
1. In PROGRAM mode, press the
PROGRAM key . The screen may
go blank for a moment. The
SITRANS LR 300 returns to RUN mode.
(P001) mode of measurement (P006) empty distance
(P002) process material (P007) span
(P003) measurement response (P837) Auto False Echo Suppression
(P004) antenna configuration (P838) Auto False Echo Suppression Distance
(P005) units