Siemens SX Series User's Guide Page 56

  • Download
  • Add to my manuals
  • Print
  • Page
    / 72
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 55
56 / 72
Siemens Desigo SX Open - SX Configurator, V2.1 CM110702en_06
Building Technologies Worksheets in SX Configurator 20 Mar 2012
5.6 BACnet Device sheet
Figure 5-33
All the information about the "virtual" BACnet devices is saved here.
It is best to assign the BACnet objects according to the subsystem or device to be
integrated, to achieve a clear, hierarchical object structure on the BACnet side.
Column Description
Instance
Instance of the BACnet device object.
The instance must be unique. It is also used as a reference in the Configuration
sheet.
Keyname
This is normally identical to the BACnet object name. The key name is interpreted
on the Desigo side as the User Designation.
Object Name
Name of the BACnet object. This can be derived automatically from the OPC
name by SX Configurator, provided this option was enabled before the OPC
import.
The object name is interpreted on the Desigo side as the Technical Designation.
Description
Description of the object.
Model Name
Individual description of the SX application, displayed in the device object property
Model_Name.
Location
Individual description of the location, displayed in the device object property
Location.
Force Update
See Configuration Sheet
Device Type
Empty = a BACnet device usable in SX BACnet Server (Configuration Sheet)
T = Device for SX Trend Server
Page view 55