Siemens Desigo SX Open - SX Configurator, V2.1 CM110702en_06
Building Technologies Worksheets in SX Configurator 20 Mar 2012
5.11 Functions sheet
Figure 5-38
The Function sheet is for entry of the predefined functions available via the
function block library, PRJLib.dll.
Only the functions that are actually needed in the main Configuration sheet
should be described.
Column Description
Function Name
Function name
Number of extra
Parameters
Number of optional extra parameters
Description
Descriptive text
Inverse Function
Inverse function, for use in cases where the function is used for signal mapping.
Library Prefix
Empty for functions located in PRJLib and EXT for mapping functions located in
a private mapping library.
For more information on the functions for signal and function mapping, refer to the
SX Open Engineering Guidelines [1].
5.12 BACnet Client sheet
Figure 5-39
SX Open normally operates as a BACnet server for the purpose of reading data
from third-party devices or systems for various uses in Desigo..
In the reverse process, however, where data is to be transmitted from Desigo to
third-party devices or systems, SX Open must also be able to act as a client on the
BACnet side. In SX Open this facility is also included as an autonomous function,
allowing the interconnection of various BACnet objects. This means, for example,
that a connection (and hence the mapping of a value) can be configured between a
Desigo PX BACnet object and an SX BACnet object. As soon as there is a change
of value in the PX object, the value is transmitted to the connected SX object. As
this, in turn, is connected to OPC, the value is also output on the OPC side.