Siemens Desigo SX Open - SX Configurator, V2.1 CM110702en_06
Building Technologies SX configuration workflow 20 Mar 2012
3.7 Editing the main configuration sheet
The worksheet and individual values are described in detail in section 5.2.
Following the import of the OPC data, the OPC section is already completed. To
complete the SX configuration, the remaining data must now be added.
All the imported OPC items must now be assigned to the appropriate BACnet
objects and properties in the BACnet section of the sheet.
For each mapping rule (= one row), other, optional functions such as alarm, trend
or mapping functions can be assigned and enabled.
3.7.1 Completing the OPC section
Column Step Procedure
OPC Access Rights
User inputs in this field are ignored
OPC Data type
User inputs in this field are ignored
VT_ARRAY Index 1
If a value exists as a VT_Array, specify which index of the value array is
to be mapped.
OPC Server Ref
(required)
2
The reference to the relevant OPC server is automatically imported from
the OPC Server sheet.
OPC Group Update Rate
(optional)
3
Overwrite individual items as necessary. The default update rate is
defined for each server in the OPC Server sheet.
If more than one OPC group with the same update rate is required, enter
update rates which differ by 1:
e.g. 800, 801, 802 etc.
Item Set Ref
(optional)
4
Enter the reference from the Item Set sheet
Device Set Ref
(optional)
5
Enter the reference from the Device Set sheet