Siemens Desigo SX Open - SX Configurator, V2.1 CM110702en_06
Building Technologies Worksheets in SX Configurator 20 Mar 2012
5.2.4 BACnet information for binary objects
Column Description
Polarity
(optional)
Polarity can be used to change an OPC item to positive logic, i.e. 0 as passive
state and 1 as active state.
Active Text
(optional)
Active text assigns a value for present-value 1.
Inactive Text
(optional)
Passive text assigns a value for present-value 0.
Min Off Time
(optional)
Min Off Time describes how long present-value stays at 0 before a change back to
1 is allowed again.
Min On Time
(optional)
Min On Time describes how long present-value stays at 1 before a change back to
0 is allowed again.
5.2.5 BACnet information for multistate objects
Column Description
No. of States
(required)
SX Open supports multistate-objects with up to 127 states. With No. of States the
actual number of used states is assigned.
State Text Ref State Text Ref is a number which references to State sheet. In State sheet there is for
every possible state a text to describe the meaning of this state.
No. of States and the number of text entries in the appropriate State sheet line
must be in sync.