Siemens Desigo SX Open - SX Configurator, V2.1 CM110702en_06
Building Technologies Worksheets in SX Configurator 20 Mar 2012
Column Description
Describes how to get the monitored value:
0 = use confirmed COV notification
-1 = use unconfirmed COV notification
Log interval
>0 = poll monitored object and use supplied value as poll interval
Buffer size
Size of the temporary trend buffer for each object. The amount of space required
for the trend log objects in the working memory of the SX PC depends on their
number and on the buffer size, and is in direct competition with other applications,
e.g. other SX components.
The buffer size should therefore be defined so as to achieve the optimum
relationship between data logging (LogInterval) and storage in Desigo Insight.
Recommendation Desigo generally limits the size of the trend log object buffer to a maximum of
5000 entries. For SX Open there is also no point in generating buffers that are
larger than this.
COV resubscripiton
interval
Describes the time between COV resubscription of a monitored object.
Currently only a COV resubscription of 0 (unlimited lifetime) is supported.
Client COV Increment
Describes the COV increment between two values received or read before storing
a new value in trendlog buffer.
Start time
When to start logging of data.
Stop time
When to stop logging of data.
Describes the behavior, if log buffer is full:
0 = overwrite the oldest entries in log buffer
Stop when full
1 = stop logging further data
Record count
This value may not be modified, it is used if an upload of trendlog objects occurs
Notification class
The value of the first active row will be used as notification class for all trendlog
objects. If different values are entered in different rows all values will be adjusted
to the value of the first active row.
Notification threshold
The amount of data in trendlog buffer before an event will be sent to all registered
recipients. If the warning limit is reached (BACnet property "Notification
Threshold"), the complete memory content is transferred to a BACnet client for
evaluation and archiving. It is advisable to set the warning limit at 40 to 60%.
The trended values can also be logged in text form in a file. This can be useful in
the commissioning phase, for example, when a trend upload to a BACnet client is
not yet possible.
For more information on the trend function in SX Configurator, refer to the Engineering
Guidelines [1].
Trend log file archive