Siemens Desigo SX Open - SX Configurator, V2.1 CM110702en_06
Building Technologies Worksheets in SX Configurator 20 Mar 2012
Column Description
Item Set Ref
Reference to an Item Set from the sheet of the same name.
Can be used for this
type of import.
Device Set Ref
Reference to a Device Set from the sheet of the same name.
Not used for this
type of import.
Depending on the number of items, the number of changes-of-value per unit of
time and the use of the values on the BACnet side, it is therefore advisable to
select update rates that are as long as possible, to avoid unnecessarily impairing
the performance of SX Open. If several groups are to be formed with the same
update rate, the update rates entered must vary by milliseconds, e.g. 1000ms,
1001ms, 1002ms, etc.
For OPC items which are VT_ARRAYS, each element of an array (matrix) uses one
row in the Configuration sheet.
SX Open supports only a fixed number of elements per VT_ARRAY.
For data imported from the OPC source, only the first row of the VT_ARRAY is
displayed. If other elements of the array are to be mapped, copy the row and
modify the array index and BACnet object name and keyname accordingly.
Figure 5-13
Note
VT_ARRAYs